Generator neutral grounding resistor panel
1. ABOUT US
Baoding Tianwei Hengtong Electric Co., Ltd is a leading professional manufacture of power system neutral grounding products, mainly including: neutral grounding resistors for transformer or generator, transformer neutral grounding protection device, arc suppression coils, arc flash protection device. Our products have been exported to more than 40 countries and regions, such as Turkey, Russia, India, Malaysia ,France and so on.
2.INTRODUCTION
THT-FZG Neutral Grounding Resistors cubicle is a complete set of equipment specially used for the power generator’s neutral point adapts the high resistance grounding. Generator Neutral shall be Non-effectively earthed through a single phase transformer with its secondary winding loaded with a suitable resistance. This method permits sensitive ground fault protection and at the same time limits the ground fault current to a low value, thus minimizing damage at fault point.
3.PRINCIPLE
If a system has a neutral point, as with a wye connected generator, there are two methods for arranging grounding equipment. The simplest method: the resistor is connected directly from the neutral point to ground. The other method, using a single phase transformer connected from a wye point to ground. The resistance value reduced by the square of the turns ration of the transformer.
The –FZG type generator neutral grounding resistor is designed as the second method to protect the generator from earth fault damage.
4. SITE CONDITION
a Ambient temperature: -40°C~60°C
b Altitude: less than 4000m
c Relative humidity: less than 95% (25°C)
d Rated frequency: 50/60HZ
a Material of enclosure: stainless steel or aluminum zinc plate with high corrosion-resistance.
b Intellect controlled unit: monitor the unbalanced current, the resistor plate, the grounding transformer and the enclosure temperature. It can also transmit the earth fault information to the controlling room.
c Resister type: stainless steel
d Location: outdoor/indoor
5.NORMAL PARAMETER TABLE
Generator capacity (MW) | 100/125 | 200 | 300 | 600 | 900/1000 | ||||
Rated Voltage (kV) | 10.5 | 13.8 | 15.75 | 18 | 20 | 20 | 24 | 24 | 27 |
Max. ground fault current(A) | 4 | 5 | 6 | 8 | 10 | ||||
Primary Voltage of sign phase grounding transformer (kV) | 10.5/√3 | 13.8/√3 | 15.75/√3 | 18/√3 | 20/√3 | 20/√3 | 24/√3 | 24/√3 | 27/√3 |
Secondary Voltage of sign phase grounding transformer (kV) | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | ||||
Grounding transformer capacity (kVA) | 30 | 30 | 50 | 50 | 63 | ||||
Resistance on the secondary | 1.0 | 0.8 | 0.5 | 0.4 | 0.3 |
6. ORDERING NOTES:
a Rated voltage of the system
b Grounding transformer capacity
c Material of the cubicle, IP level, and installation.
d Rated time
e Resistance value
f Require the intelligent controller or not.
( function(){ var aBigImageSrc = [ 'http://i01.i.aliimg.com/photo/v3/609687019_1/Generator_neutral_grounding_resistor_panel.jpg' , 'http://i01.i.aliimg.com/photo/v3/609687019_2/Generator_neutral_grounding_resistor_panel.jpg' ]; var oProductShow = new AE.run.minisite.productShow(); oProductShow.init( { 'aImgSrc': aBigImageSrc } ); } )(); Generator neutral grounding resistor panel